The Electric Shutoff Assembly G319-A is the standard shutoff supplied with the G300B system. Features provided with this shutoff include the following:
1. A “Fail Safe Mode” consisting of a Normally Open (N/O) Contactor that is energized continually. Activation due to a fire will open the contactor, disconnecting "electrical power” supply lines to the stove.
2. Standard interface interconnect cable will be provided or optional “Sonic Receiver” board upon request.
3. Two extra set of dry contacts for switching external devices during system activation are provided via opyional Interface Enclosure Assembly.
4. The shutoff also has a latching feature to eliminate any possibility of an automatic reset of the power supply after a fire. To restore power to the stove simply disconnect power to the electric shut off device by flipping its breaker off and then on again.
Gas
The Gas Shutoff Assembly G316-A is the standard shutoff supplied with the G300B system. Features provided with this shutoff include the following:
1. A “Fail Safe Mode” consisting of a Normally Closed (N/C) valve that is energized continually. Loss of power or activation due to a fire will close the valve, shutting off “gas flow” and “electrical power” to the stove.
2. Standard interface interconnect cable will be provided or optional “Sonic Receiver” board upon request.
3. An extra set of dry contacts for switching external devices during system activation are provided.
4. The shutoff also has a manual “power reset” feature to eliminate any possibility of an automatic reset activation of the valve occurring after a fire or loss of power.